Siemens SINAMICS S110 List Manual page 1215

Hide thumbs Also See for SINAMICS S110:
Table of Contents

Advertisement

A32412 (F, N)
Encoder 2: Error bit set in the serial protocol
Message value:
%1
Drive object:
SERVO_S110-CAN, SERVO_S110-DP, SERVO_S110-PN
Reaction:
NONE
Acknowledge:
NONE
Cause:
The encoder sends a set error bit via the serial protocol.
Alarm value (r2124, binary interpretation):
Bit 0: Fault bit in the position protocol.
Bit 1: Alarm bit in the position protocol.
Remedy:
- carry out a POWER ON (power off/on) for all components.
- check that the encoder cables are routed in compliance with EMC.
- check the plug connections
- replace the encoder.
Reaction upon F:
NONE (IASC/DCBRAKE, OFF1, OFF2, OFF3, STOP1, STOP2)
Acknowl. upon F:
IMMEDIATELY
Reaction upon N:
NONE
Acknowl. upon N:
NONE
A32414 (F, N)
Encoder 2: Amplitude error track C or D (C^2 + D^2)
Message value:
C track: %1, D track: %2
Drive object:
SERVO_S110-CAN, SERVO_S110-DP, SERVO_S110-PN
Reaction:
NONE
Acknowledge:
NONE
Cause:
The amplitude (C^2 + D^2) of track C or D of the encoder or from the Hall signals, is not within the tolerance band-
width.
Alarm value (r2124, interpret hexadecimal):
yyyyxxxx hex:
yyyy = Signal level, track D (16 bits with sign).
xxxx = Signal level, track C (16 bits with sign).
The nominal signal level of the encoder must lie in the range 375 mV to 600 mV (500 mV -25/+20 %).
The response thresholds are < 230 mV (observe the frequency response of the encoder) and > 750 mV.
A signal level of 500 mV peak value corresponds to the numerical value 5333 hex = 21299 dec.
Note:
If the amplitude is not within the tolerance bandwidth, then it cannot be used to initialize the start position.
Remedy:
- check that the encoder cables are routed in compliance with EMC.
- check the plug connections
- replace the encoder or encoder cable
- check the Sensor Module (e.g. contacts).
- check the Hall sensor box
Reaction upon F:
NONE (IASC/DCBRAKE, OFF1, OFF2, OFF3, STOP1, STOP2)
Acknowl. upon F:
IMMEDIATELY
Reaction upon N:
NONE
Acknowl. upon N:
NONE
N32415 (F, A)
Encoder 2: Amplitude alarm track A or B (A^2 + B^2)
Message value:
Amplitude: %1, Angle: %2
Drive object:
SERVO_S110-CAN, SERVO_S110-DP, SERVO_S110-PN
Reaction:
NONE
Acknowledge:
NONE
Cause:
The amplitude (root of A^2 + B^2) for encoder 2 exceeds the permissible tolerance.
Alarm value (r2124, interpret hexadecimal):
yyyyxxxx hex:
yyyy = Angle
xxxx = Amplitude, i.e. root from A^2 + B^2 (16 bits without sign)
The nominal signal level of the encoder must lie in the range 375 mV to 600 mV (500 mV -25/+20 %).
The response threshold is < 300 mV (observe the frequency response of the encoder).
A signal level of 500 mV peak value corresponds to the numerical value 299A hex = 10650 dec.
© Siemens AG 2012 All Rights Reserved
SINAMICS S110 List Manual (LH7), 06/2012, 6SL3097-4AP10-0BP3
Faults and alarms
List of faults and alarms
3-1215