Siemens SINAMICS S110 List Manual page 700

Hide thumbs Also See for SINAMICS S110:
Table of Contents

Advertisement

Parameter
List of parameters
Value:
0:
1:
2:
3:
4:
5:
6:
7:
8:
9:
9999: Do not calculate
p20182
PST 0 run sequence / PST 0 RunSeq
CU_S110-CAN,
Can be changed: T
CU_S110-DP,
Data type: Unsigned16
CU_S110-PN,
P-Group: -
SERVO_S110-CAN
Not for motor type: -
(FBLOCKS),
SERVO_S110-DP
(FBLOCKS),
SERVO_S110-PN
(FBLOCKS)
Min
0
Description:
Setting parameter for the run sequence of instance PST 0 within the run-time group set in p20181.
Note:
The function blocks with a lower run sequence value are calculated before function blocks with a higher run
sequence value.
p20183[0...1]
BI: PST 1 inputs / PST 1 inputs
CU_S110-CAN,
Can be changed: T
CU_S110-DP,
Data type: Unsigned32 / Binary
CU_S110-PN,
P-Group: -
SERVO_S110-CAN
Not for motor type: -
(FBLOCKS),
SERVO_S110-DP
(FBLOCKS),
SERVO_S110-PN
(FBLOCKS)
Min
-
Description:
Sets the signal source for input pulse I and the reset input R of instance PST 1 of the pulse extension element.
Index:
[0] = Input pulse I
[1] = Reset input R
p20184
PST 1 pulse duration in ms / PST 1 pulse_dur ms
CU_S110-CAN,
Can be changed: T
CU_S110-DP,
Data type: FloatingPoint32
CU_S110-PN,
P-Group: -
SERVO_S110-CAN
Not for motor type: -
(FBLOCKS),
SERVO_S110-DP
(FBLOCKS),
SERVO_S110-PN
(FBLOCKS)
Min
0.00
Description:
Setting parameter for pulse duration T in milliseconds of instance PST 1 of the pulse extension element.
1-700
Run-time group 0
Run-time group 1
Run-time group 2
Run-time group 3
Run-time group 4
Run-time group 5
Run-time group 6
Run-time group 7
Run-time group 8
Run-time group 9
Calculated: -
Dynamic index: -
Units group: -
Scaling: -
Max
7999
Calculated: -
Dynamic index: -
Units group: -
Scaling: -
Max
-
Calculated: -
Dynamic index: -
Units group: -
Scaling: -
Max
60000.00
© Siemens AG 2012 All Rights Reserved
SINAMICS S110 List Manual (LH7), 06/2012, 6SL3097-4AP10-0BP3
Access level: 1
Func. diagram: 7234
Unit selection: -
Expert list: 1
Factory setting
490
Access level: 1
Func. diagram: 7234
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 1
Func. diagram: 7234
Unit selection: -
Expert list: 1
Factory setting
0.00

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents