A03510 (F, N)
CU: Calibration data not plausible
Message value:
%1
Drive object:
CU_S110-CAN, CU_S110-DP, CU_S110-PN
Reaction:
NONE
Acknowledge:
NONE
Cause:
During booting, the calibration data for the analog inputs is read and checked with respect to plausibility.
At least one calibration data point was determined to be invalid.
Remedy:
- power down/power up the power supply for the Control Unit.
- check the DRIVE-CLiQ connection.
If it reoccurs, replace the module.
In principle, operation could continue.
The analog channel involved possibly does not achieve the specified accuracy.
Reaction upon F:
NONE (OFF1, OFF2)
Acknowl. upon F:
IMMEDIATELY (POWER ON)
Reaction upon N:
NONE
Acknowl. upon N:
NONE
A03510 (F, N)
TM: Calibration data not plausible
Message value:
%1
Drive object:
SERVO_S110-CAN, SERVO_S110-DP, SERVO_S110-PN
Reaction:
NONE
Acknowledge:
NONE
Cause:
During ramp-up, the Terminal Module 31 (TM31) calibration data is read in and checked for plausibility.
At least one calibration data point was determined to be invalid.
Alarm value (r2124, binary interpretation):
Bit 1: 10 V value, analog input 0 invalid.
Bit 3: 10 V value, analog input 1 invalid.
Bit 4: Offset, analog output 0 invalid.
Bit 5: 10 V value, analog output 0 invalid.
Bit 6: Offset, analog output 1 invalid.
Bit 7: 10 V value, analog input 1 invalid.
Remedy:
- power down/power up the power supply for the Control Unit.
- check the DRIVE-CLiQ connection.
If it reoccurs, replace the module.
In principle, operation could continue.
The analog channel involved possibly does not achieve the specified accuracy.
Reaction upon F:
NONE (OFF1, OFF2)
Acknowl. upon F:
IMMEDIATELY (POWER ON)
Reaction upon N:
NONE
Acknowl. upon N:
NONE
A05000 (N)
Power unit: Overtemperature heat sink AC inverter
Message value:
-
Drive object:
SERVO_S110-CAN, SERVO_S110-DP, SERVO_S110-PN
Reaction:
NONE
Acknowledge:
NONE
Cause:
The alarm threshold for overtemperature at the inverter heat sink has been reached. The response is set using
p0290.
If the temperature of the heat sink increases by an additional 5 K, then fault F30004 is initiated.
Remedy:
Check the following:
- is the ambient temperature within the defined limit values?
- have the load conditions and the load duty cycle been appropriately dimensioned?
- has the cooling failed?
Reaction upon N:
NONE
Acknowl. upon N:
NONE
© Siemens AG 2012 All Rights Reserved
SINAMICS S110 List Manual (LH7), 06/2012, 6SL3097-4AP10-0BP3
Faults and alarms
List of faults and alarms