Parameter
List of parameters
p9905
Device specialization / Specialization
CU_S110-CAN,
Can be changed: C1(1)
CU_S110-DP,
Data type: Unsigned16
CU_S110-PN
P-Group: Topology
Not for motor type: -
Min
0
Description:
With p9905 = 1, the serial numbers and the hardware versions of all of the components are transferred from the
actual topology into the target topology and a new comparison is started..
For this device specialization, the components of the target topology may only differ from those of the actual topol-
ogy by the serial numbers.
With p9905 = 2, the serial numbers, the hardware versions and the order numbers of all of the components are
transferred from the actual topology into the target topology and a new comparison is started..
For this device specialization, the components of the target topology may only differ from those of the actual topol-
ogy by the serial numbers and order numbers.
Note:
p9905 is automatically set to 0 at the end of the operation.
In order to permanently accept the data, it is necessary to save in a non-volatile fashion (p0977).
p9910
Transfer additional components into the target topology / Transfer comp
CU_S110-CAN,
Can be changed: C1(1)
CU_S110-DP,
Data type: Integer16
CU_S110-PN
P-Group: Topology
Not for motor type: -
Min
0
Description:
Transfer additional inserted DRIVE-CLiQ components into the target topology and add the appropriate drive objects
to the project.
Value:
0:
1:
2:
3:
4:
5:
6:
p9915
DRIVE-CLiQ data transfer error shutdown threshold master / DLQ fault master
CU_S110-CAN,
Can be changed: C1(1)
CU_S110-DP,
Data type: Unsigned32
CU_S110-PN
P-Group: Topology
Not for motor type: -
Min
0000 hex
Description:
Only for internal Siemens service purposes.
p9916
DRIVE-CLiQ data transfer error shutdown threshold slave / DLQ fault slave
CU_S110-CAN,
Can be changed: C1(1)
CU_S110-DP,
Data type: Unsigned32
CU_S110-PN
P-Group: Topology
Not for motor type: -
Min
0000 hex
Description:
Only for internal Siemens service purposes.
1-614
No selection
Drive object type SERVO
Drive object type VECTOR
SINAMICS GM (DFEMV & VECTORMV)
SINAMICS SM (AFEMV & VECTORMV)
SINAMICS GL (VECTORGL)
SINAMICS SL (VECTORSL)
Calculated: -
Dynamic index: -
Units group: -
Scaling: -
Max
2
Calculated: -
Dynamic index: -
Units group: -
Scaling: -
Max
6
Calculated: -
Dynamic index: -
Units group: -
Scaling: -
Max
0007 07FF hex
Calculated: -
Dynamic index: -
Units group: -
Scaling: -
Max
0007 07FF hex
© Siemens AG 2012 All Rights Reserved
SINAMICS S110 List Manual (LH7), 06/2012, 6SL3097-4AP10-0BP3
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 1
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 4
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0007 02FF hex
Access level: 4
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0007 02FF hex