Fault value (r0949, decimal interpretation):
The two parameters in coded form, that refer to the same component number.
First parameter:
Index: First and second decimal place (99 for EDS, not assigned DDS)
Parameter number: Third decimal place (1 for p0187, 2 for p0188, 3 for p0189, 4 for EDS not assigned DDS)
Drive number: Fourth and fifth decimal place
Second parameter:
Index: Sixth and seventh decimal place (99 for EDS, not assigned DDS)
Parameter number: Eighth decimal place (1 for p0187, 2 for p0188, 3 for p0189, 4 for EDS, not assigned DDS)
Drive number: Ninth and tenth decimal place
See also: p0141 (Encoder interface (Sensor Module) component number)
Remedy:
Correct the double use of a component number using the two parameters coded in the fault value.
A07514 (N)
Drive: Data structure does not correspond to the interface module
Message value:
-
Drive object:
SERVO_S110-CAN, SERVO_S110-DP, SERVO_S110-PN
Reaction:
NONE
Acknowledge:
NONE
Cause:
The interface mode "SIMODRIVE 611 universal" was set (p2038 = 1) and the data structure does not correspond to
this mode.
For the data structure, the following rule must be complied with.
Within the group of 8 drive data sets, the assignment to the motor data set must be set the same:
p0186[0] = p0186[1] = ... = p0186[7]
p0186[8] = p0186[9] = ... = p0186[15]
p0186[16] = p0186[17] = ... = p0186[23]
p0186[24] = p0186[25] = ... = p0186[31]
See also: p0180 (Number of Drive Data Sets (DDS)), p0186 (Motor Data Sets (MDS) number), p2038 (IF1 PROFId-
rive STW/ZSW interface mode)
Remedy:
- structure the data according to the rules of the "SIMODRIVE 611 universal" interface mode.
- check the interface mode (p2038).
Reaction upon N:
NONE
Acknowl. upon N:
NONE
F07515
Drive: Power unit and motor incorrectly connected
Message value:
%1
Drive object:
SERVO_S110-CAN, SERVO_S110-DP, SERVO_S110-PN
Reaction:
OFF2
Acknowledge:
IMMEDIATELY
Cause:
A power unit (via PDS) was assigned to a motor (via MDS) in a drive data set that is not connected in the target
topology.
Alarm value (r2124, interpret decimal):
Number of the incorrectly parameterized drive data set.
Remedy:
- assign the drive data set to a combination of motor and power unit permitted by the target topology.
- adapt the target topology.
See also: p0121 (Power unit component number), p0131 (Motor component number), p0186 (Motor Data Sets
(MDS) number)
F07516
Drive: Re-commission the data set
Message value:
%1
Drive object:
SERVO_S110-CAN, SERVO_S110-DP, SERVO_S110-PN
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
The assignment between the drive data set and motor data set (p0186) or between the drive data set and the
encoder data set was modified (p0187). This is the reason that the drive data set must re-commissioned.
Fault value (r0949, decimal interpretation):
Drive data set to be re-commissioned.
Remedy:
Commission the drive data set specified in the fault value (r0949).
© Siemens AG 2012 All Rights Reserved
SINAMICS S110 List Manual (LH7), 06/2012, 6SL3097-4AP10-0BP3
Faults and alarms
List of faults and alarms
3-1089