Possible causes:
- stop request from the Control Unit.
- subsequent response to the message C30714 "SI Motion: Safely limited speed exceeded".
See also: p9353 (SI Motion transition time STOP D to SOS (processor 2)), p9553 (SI Motion transition time STOP
D to SOS (processor 1))
Remedy:
- remove the cause of the fault at the control.
- carry out a diagnostics routine for message C30714.
This message can only be acknowledged via the Terminal Module 54F (TM54F) or PROFIsafe.
Note:
SI: Safety Integrated
SOS: Safe Operating Stop / SBH: Safe operating stop
C30710
SI Motion MM: STOP E initiated
Message value:
-
Drive object:
SERVO_S110-CAN, SERVO_S110-DP, SERVO_S110-PN
Reaction:
NONE
Acknowledge:
IMMEDIATELY (POWER ON)
Cause:
The drive is stopped via a STOP E (retraction motion).
"Safe Operating Stop" (SOS) is activated after the parameterized timer has expired.
Possible causes:
- stop request from the higher-level control.
- subsequent response to the message C30714 "SI Motion: Safely limited speed exceeded".
See also: p9354 (SI Motion transition time STOP E to SOS (processor 2)), p9554 (SI Motion transition time STOP E
to SOS (processor 1))
Remedy:
- remove the cause of the fault at the control.
- carry out a diagnostics routine for message C30714.
This message can only be acknowledged via the Terminal Module 54F (TM54F) or PROFIsafe.
Note:
SI: Safety Integrated
SOS: Safe Operating Stop / SBH: Safe operating stop
C30711
SI Motion MM: Defect in a monitoring channel
Message value:
%1
Drive object:
SERVO_S110-CAN, SERVO_S110-DP, SERVO_S110-PN
Reaction:
NONE
Acknowledge:
IMMEDIATELY (POWER ON)
Cause:
When cross-checking and comparing the two monitoring channels, the drive detected a difference between the input
data or results of the monitoring functions and initiated a STOP F. One of the monitoring functions no longer reliably
functions - i.e. safe operation is no longer possible.
If at least one monitoring function is active, then after the parameterized timer has expired, the message C30701 "SI
Motion: STOP B initiated" is output. The message is output with message value 1031 when the Sensor Module hard-
ware is replaced.
The following message values may also occur in the following cases if the cause that is explicitly mentioned does
not apply:
- differently parameterized cycle times (p9500/p9300, p9511/p9311).
- differently parameterized axis types (p9502/p9302).
- excessively fast cycle times (p9500/p9300, p9511/p9311).
- incorrect synchronization.
Message value (r9749, interpret decimal):
0 ... 999: Number of the cross-checked data that resulted in this message. Refer to safety message C01711for a
description of the individual data.
The significance of the individual message values is described in safety message C01711 of the Control Unit.
1000: Watchdog timer has expired. Too many signal changes have occurred at safety-relevant inputs.
1001: Initialization error of watchdog timer.
1005: Pulses already suppressed for test stop selection.
1011: Acceptance test status between the monitoring channels differ.
1012: Plausibility violation of the actual value from the encoder.
1020: Cyc. communication failure between the monit. cycles.
1021: Cyc. communication failure between the monit. channel and Sensor Module.
1023: Error in the effectiveness test in the DRIVE-CLiQ encoder
1030: Encoder fault detected from another monitoring channel.
© Siemens AG 2012 All Rights Reserved
SINAMICS S110 List Manual (LH7), 06/2012, 6SL3097-4AP10-0BP3
Faults and alarms
List of faults and alarms
3-1157