Siemens SINAMICS S110 List Manual page 810

Hide thumbs Also See for SINAMICS S110:
Table of Contents

Advertisement

Signal sources for CU_ZSW1
Signal
Meaning
CU_ZSW1.0
Reserved
CU_ZSW1.1
Reserved
CU_ZSW1.2
Reserved
CU_ZSW1.3
1 = Fault present
CU_ZSW1.4
Reserved
CU_ZSW1.5
Reserved
CU_ZSW1.6
Reserved
CU_ZSW1.7
1 = Alarm present
CU_ZSW1.8
1 = System time synchronized
CU_ZSW1.9
1 = Alarm is not present
CU_ZSW1.10
1 = Fault not present
CU_ZSW1.11
1 = Safety-Message/signal not present
CU_ZSW1.12
Slave sign-of-life bit 0
CU_ZSW1.13
Slave sign-of-life bit 1
CU_ZSW1.14
Slave sign-of-life bit 2
CU_ZSW1.15
Slave sign-of-life bit 3
<1> Used in telegrams 390 and 391.
<2> The ZSW1 is generated using the binector-connector converter (BI: p2080[0...15], inversion: p2088[0].0...p2088[0].15)
1
2
DO: CU_S110
PROFIdrive - CU_ZSW1 status word 1 Control Unit interconnection
Interconnection
parameters
p2081[3] = r2139.3
p2081[7] = r2139.7
p2081[8] = r0899.8
p2081[9] = r3114.9
p2081[10] = r3114.10
p2081[11] = r3114.11
Implicitly
interconnected
3
4
[Function diagram]
[Function diagram]
Internal status word
signal source
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
5
6
fp_2496_98_eng.vsd
25.01.10 V04.04.00
PROFIdrive sampling time
<1>
<1>
Refer to [1020.7]
Inverted
<2>
-
-
-
-
-
-
-
-
-
-
7
8
Function diagram
- 2496 -
SINAMICS S110