6.2.5 Problem starting or connecting the FlexPendant
Description
The FlexPendant is not responding, either completely or intermittently.
No entries are possible, and no functions are available.
The FlexPendant starts but does not display the main interface.
xx1900000917
Required test equipment
Equipment needed for troubleshooting:
Equipment
Multimeter
Insulating gloves
Circuit diagram - OmniCore C30, Circuit dia-
gram - OmniCore C30 for IRB 14050, Circuit
diagram - OmniCore C30 for CRB 15000
Preparations
1
2
Product manual - OmniCore C30
3HAC060860-001 Revision: P
Note
If protective gloves are used, these must be compatible with touchscreens when
using the FlexPendant.
Action
Make sure that the controller is switched on.
Wait 30 s - 1 min to enable start-up sequence.
Check the FlexPendant for errors and warnings.
© Copyright 2019-2022 ABB. All rights reserved.
6.2.5 Problem starting or connecting the FlexPendant
Note
3HAC059896-009, 3HAC063898-009,
3HAC072448-009
6 Troubleshooting
Continues on next page
517