Product manual - OmniCore C30
3HAC060860-001 Revision: P
6.2.5 Problem starting or connecting the FlexPendant
Action
Check that the connection from the robot signal
exchange proxy to the main computer is ok:
K2.X8 - A2.X6
K2.X2 - A2.X1
K2.X12 - A2.K3.X6,7
K2.X3 - A2.K3.X1
If possible, test by connecting another FlexPend-
ant. This is to eliminate the FlexPendant and cable
as error sources; Test the FlexPendant with a
different controller to eliminate the controller as
error source.
Check that the FlexPendant works normally.
Tip
This is detailed in section
FlexPendant on page
529.
© Copyright 2019-2022 ABB. All rights reserved.
Note
If it is not ok, contact your local
ABB.
Troubleshooting the
6 Troubleshooting
Continued
If any connection fails, re-
pair the connection and go
to step six.
If the connections are ok, go
to the next step.
521