6 Troubleshooting
6.2.2 Start-up failure
Continued
2
3
4
5
6
510
Action
Look at the LED PS.
Look at the LED MS.
Look at the LEDs PC and HMI.
Look at the LEDs PC PWR, PC HDD, and PC
STAT.
If the problem remains, contact ABB.
Tip
For more details, see Circuit diagram - OmniCore C30, Circuit diagram - OmniCore
C30 for IRB 14050, Circuit diagram - OmniCore C30 for CRB 15000.
© Copyright 2019-2022 ABB. All rights reserved.
Note
LED PS should be green.
If not, see
Troubleshooting
the power supply on
page
550.
If the power supply is ok,
see
Troubleshooting the
power unit on page
If the power unit is ok, check
that the power inlet is prop-
erly connected and the
power inlet switch is turned
on.
For more details about the LEDs,
see
Troubleshooting the robot sig-
nal exchange proxy on page
LED MS should be green.
If not, see
Troubleshooting
the robot signal exchange
proxy on page
555.
LED PC and LED HMI should be
green.
If not, see
Troubleshooting
the robot signal exchange
proxy on page 555
For more details about the LEDs,
see
Troubleshooting the main
computer on page
547.
Product manual - OmniCore C30
3HAC060860-001 Revision: P