ABB OmniCore C30 Product Manual page 539

Hide thumbs Also See for OmniCore C30:
Table of Contents

Advertisement

Description
STATUS LED
(red/green)
LINK
LINK
RF, signal
strength status
LEDs
Required test equipment
Equipment needed for troubleshooting:
Equipment
Multimeter
Insulating gloves
Preparations
1
2
3
Product manual - OmniCore C30
3HAC060860-001 Revision: P
6.3.6 Troubleshooting the connected services gateway
Significance
Startup sequence:
1 Red continuously: Default at power up.
2 Red, flashing: Power on self-test ongoing, operating system is
loading.
3 Green flashing: Loading application.
4 Green solid: Startup completed OK.
If the LED does not turn steady green after 30-60sec, it can be used to
identify the following issues:
Fault indication:
No color: Power to the unit is missing.
Red, solid or flashing: Internal error. Replace the unit.
Green, flashing continuously: Communication error to another
module, view error messages.
For the connected services 3G, an orange LED indicator, externally visible
on the front, indicates the status of the 3G connection.
Orange:
ON, flashing: 3G modem on, searching network.
ON, solid: 3G modem on and connected to network.
For the connected services Wi-Fi, an orange LED indicator, externally
visible on the front, indicates the status of the Wi-Fi connection.
Orange:
ON, flashing: Wi-Fi transceiver on, searching network.
ON, solid: Wi-Fi transceiver on and connected to network.
Three (3) LEDs indicating the Wi-Fi or 3G signal level.
ON: The unit is connected to the network and working ok.
OFF: Problem with connector, antenna, or sim card.
Action
Check the FlexPendant for errors and warnings.
Power the controller off. Wait one minute, power the controller on.
Wait 30-60 seconds after power-on.
Make sure that the control system power is in run-time mode.
© Copyright 2019-2022 ABB. All rights reserved.
6 Troubleshooting
Note
Continues on next page
Continued
539