Product manual - OmniCore C30
3HAC060860-001 Revision: P
6.3.11 Troubleshooting the robot signal exchange proxy
Test
Check external safety ac-
cessories.
Measure the AC OK signal.
The robot signal exchange
proxy may be faulty, replace
it and verify that the fault has
been fixed.
© Copyright 2019-2022 ABB. All rights reserved.
Action
Use a multimeter and insulating gloves.
Measure the continuity in the connector. If there is
resistance, troubleshoot the external equipment.
Use a multimeter and insulating gloves.
The AC OK should be 0 V.
Make sure that connector X10 is connected properly
on both ends.
If the AC OK signal is 24 V, see
Troubleshooting the power unit on page
If the AC OK signal is 0 V, proceed with step
11.
How to replace the unit is detailed in
robot signal exchange proxy on page
6 Troubleshooting
Continued
532.
Replacing the
282.
561