Troubleshooting flowchart
xx1800001831
Product manual - OmniCore C30
3HAC060860-001 Revision: P
Problem starting or
connecting the FlexPendant
Check connector X4
Check LEDs:
HMI & PC
Check FlexPendant
cable
Check connection
K2.X9 to X4
Check:
K2.X8 - A2.X6
K2.X2 - A2.X1
K2.X12 - A2.K3.X6,7
K2.X3 - A2.K3.X1
Replace FlexPendant
Not starting
Start FlexPendant
Problem solved
© Copyright 2019-2022 ABB. All rights reserved.
6.2.5 Problem starting or connecting the FlexPendant
Connection not ok
Connection ok
Not lit
Green
Cable
damaged
Cable ok
Connection
not ok
Connection
not ok
Connections ok
Ok
6 Troubleshooting
Continued
Repair connection
Troubleshoot robot signal
exchange proxy K2
Replace FlexPendant
cable
Continues on next page
519