ABB OmniCore C30 Product Manual page 41

Hide thumbs Also See for OmniCore C30:
Table of Contents

Advertisement

Parameter
Vibration
Bumps
After storage, the operating conditions inside the controller must be met for at least
6 hours before switching on the controller (see
The robot controller shall only be stored indoors, in an environment that is dry and
dust-free. In addition, wind, temperature fluctuations, and condensation shall be
avoided.
Operating conditions
The table shows the allowed operating conditions for the controller.
Parameter
Minimum ambient temperature
Maximum ambient temperature
Maximum ambient altitude
Vibration
Bumps
Protection classes
Controller cabinet, inner compartment for
electronics
FlexPendant
Noise emission
Data
Noise emission
Product manual - OmniCore C30
3HAC060860-001 Revision: P
Note
The humidity conditions shall apply with the environmental conditions EN
60721-3-3, climatic class 3K3. For temperatures 0-30°C, the relative humidity
must not exceed 85%. For temperatures exceeding 30°C, the absolute humidity
must not exceed 25g/m
If the environmental conditions in EN 60721-3-3, climatic class 3K3, are not
possible to meet at the installation site, desiccant bags can be placed inside the
controller to achieve corresponding conditions. The desiccant bags must be
replaced regularly to maintain approved operating conditions.
© Copyright 2019-2022 ABB. All rights reserved.
2.2 Technical data for OmniCore C30 controller
Value
Max. Grms = 4 m/s
12.8 m/s
Max. 5 g = 50 m/s
Operating conditions on page
Value
+5°C (+41°F)
+45°C (+113°F)
2,000 m
Max. Grms = 2.86 m/s
Max. 5 g = 50 m/s
3
.
Protection class
IP20
IP54
Description
The sound pressure level one
meter away from each surface
of the controller.
2 Controller description
Continued
2
(X & Y axis), Grms =
2
(Z axis)
2
(11 ms)
2
(X, Y, Z axis)
2
(11 ms)
Note
< 60 dB(A) Leq
Continues on next page
41).
41