6 Troubleshooting
6.2.5 Problem starting or connecting the FlexPendant
Continued
Location of LEDs
xx1700001886
Detailed working procedure
1
2
3
4
5
Continues on next page
520
Action
Try resetting the FlexPendant using the reset
button located next to the USB port.
Check that the FlexPendant cable is correctly
connected to the controller through the HMI signal
connector, X4.
Check the LED PC and LED HMI, they should be
green.
Check the FlexPendant cable for any damage.
Check that the connection from the robot signal
exchange proxy to the HMI signal connector is
ok, K2.X9, 13 - X4.
© Copyright 2019-2022 ABB. All rights reserved.
Note
See Operating manual - OmniCore.
If it is not connected, repair the
connection and go to step six.
Check the pins in the connector.
If it is ok, go to the next step.
For more details about the LEDs,
see
Troubleshooting the robot sig-
nal exchange proxy on page
If the LEDs are not green,
see
Troubleshooting the ro-
bot signal exchange proxy
on page
555.
If they are ok, go to the next
step.
If damage is found, replace
the FlexPendant cable and
go to step six.
If it is ok, go to the next
step.
If it is not ok, repair the con-
nection and go to step six.
If it is ok, go to the next
step.
Product manual - OmniCore C30
3HAC060860-001 Revision: P
555.