Chapter 8 Parameters
Data Size: 32-bit
Format: Decimal
Settings: The position counter of the E-Cam Master
P5-87
PLED
Operational
Interface:
Default: 0
Control
Mode:
Range: -1073741824 ~ +1073741823
Data Size: 32-bit
Format: Decimal
Settings: When the engaging condition (P5-88.Z) of E-cam is satisfied, the pulse
P5-88■
ECON E-CAM: Activate E-Cam Control
Operational
Interface:
Default: 0x00000000
Control
Mode:
8-204
Note: 1. This parameter can be written when E-Cam stops (Please refer to
P5-88, X=0).
2. A2-L does not support E-Cam function.
E-CAM: Lead Pulse
Panel / Software
PR
Unit: -
number from the master has to exceed the setting value of this
parameter, so that E-cam is fully engaged.
In other words, E-cam engages after neglecting the lead pulse
specified by this parameter.
If the symbol of this parameter is +, it means the received forward pulse
is regarded as the lead pulse.
If the symbol of this parameter is - , it means the received reverse
pulse is regarded as the lead pulse.
Note: A2-L does not support E-Cam function.
Panel / Software
PR
Communication
Communication
ASDA-A2
Address: 05AEH
05AFH
Related Section:
7.11
Address: 05B0H
05B1H
Related Section:
7.11