18.13.2
Remote diagnostics via Teleservice adapter IE at X127
The following settings must be made for remote diagnostics via modem using a Teleservice
adapters IE (TS Adapter) that is connected at X127:
Settings in the TS Adapter required
● IP address of the adapter: 192.168.215.30, subnet mask 255.255.255.224
● IP address of the caller: 192.168.215.29
● Enable the ports for the services for S7 communication, http, HTTPS, SSH as well as
Connecting the modem for remote diagnostics
Figure 18-1
With the previously mentioned settings and the default values, in this configuration, remote
diagnostics via TS Adapter is possible without any additional changes having to be made.
SINUMERIK Operate (IM9)
Commissioning Manual, 03/2013, 6FC5397-1DP40-3BA1
These two addresses are also stored as standard in the "tcu.ini" file. If other addresses
are used, the entries "X127ModemIP" and "X127RemoteAccessIP" must be appropriately
changed in the "tcu.ini" file.
VNC (port 5900) in the firewall.