Siemens SINUMERIK 840D sl Commissioning Manual page 955

Basesoftware and operating software
Hide thumbs Also See for SINUMERIK 840D sl:
Table of Contents

Advertisement

Legend:
2.4.3
Configuration for exiting the operating software
HMI monitoring
Exiting the operating software is monitored via an own hmiexit.exe application. This
application is started implicitly via the shutdown.bat batch file. In case of error, the
application forces the operating system to shut down. An error occurs if the HMI cannot be
exited within the configured delay.
Optionally, the parameters below can be set for hmiexit in file:
E:\SITOP\hmiexit.ini.
[Actions]
#Waiting time in seconds for closing HMI Advanced applications
Wait = 120
# Action on expiration of the waiting time
ForceShutdown = True
These default settings only need to be changed if it takes longer than 120 seconds to exit the
HMI applications in an OEM installation. This configuration is not usually changed.
PCU-Basesoftware (IM8)
Commissioning Manual, 02/2012, 6FC5397-1DP40-3BA0
On - Off
1
2
+320 s
3
+160s
4
+80s
5
+40s
6
+20s
7
+10s
8
9
Delivery condition setting
Setting for operation on the PCU
2.4 PCU with SITOP UPS module
Set time/max. time
Buffer time
+5 s fixed
Disconnection
Battery operating state on/off
Configuring the system
61