4 Faults and alarms
4.2 List of faults and alarms
A02058
Trace: Time slice clock cycle for endless trace not valid
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Reaction:
NONE
Acknowledge:
NONE
Cause:
The selected time slice clock cycle cannot be used for the endless trace
Remedy:
Enter the clock cycle of an existing time slice with a cycle time >= 2 ms for up to 4 recording channels or >= 4 ms
from 5 recording channels per trace.
The existing time slices can be read out via p7901.
See also: r7901 (Sampling times)
A02059
Trace: Time slice clock cycle for 2 x 8 recording channels not valid
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Reaction:
NONE
Acknowledge:
NONE
Cause:
The selected time slice clock cycle cannot be used for more than 4 recording channels.
Remedy:
Enter the clock cycle of an existing time slice with a cycle time >= 4 ms or reduce the number of recording channels
to 4 per trace.
The existing time slices can be read out via p7901.
See also: r7901 (Sampling times)
A02060
Trace: Signal to be traced missing
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Reaction:
NONE
Acknowledge:
NONE
Cause:
- a signal to be traced was not specified.
- the specified signals are not valid.
Remedy:
- specify the signal to be traced.
- check whether the relevant signal can be traced.
A02061
Trace: Invalid signal
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Reaction:
NONE
Acknowledge:
NONE
Cause:
- the specified signal does not exist.
- the specified signal can no longer be traced (recorded).
Remedy:
- specify the signal to be traced.
- check whether the relevant signal can be traced.
A02062
Trace: Invalid trigger signal
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Reaction:
NONE
Acknowledge:
NONE
Cause:
- a trigger signal was not specified.
- the specified signal does not exist.
- the specified signal is not a fixed-point signal.
- the specified signal cannot be used as a trigger signal for the trace.
Remedy:
Specify a valid trigger signal.
A02063
Trace: Invalid data type
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Reaction:
NONE
Acknowledge:
NONE
Cause:
The specified data type to select a signal using a physical address is invalid.
Remedy:
Use a valid data type.
1068
SINAMICS G120 CU250S-2 Control Units
List Manual, 09/2017, A5E33842890