4 Faults and alarms
4.2 List of faults and alarms
F07451 (A)
LR: Position monitoring has responded
Message class:
Application/technological function faulted (17)
Reaction:
OFF1 (OFF2, OFF3)
Acknowledge:
IMMEDIATELY
Cause:
When the position monitoring time (p2545) expired, the drive had still not reached the positioning window (p2544).
- positioning window parameterized too small (p2544).
- position monitoring time parameterized too short (p2545).
- position loop gain too low (p2538).
- position loop gain too high (instability/oscillation, p2538).
- drive mechanically locked.
Remedy:
Check the causes and resolve.
F07452 (A)
LR: Following error too high
Message class:
Application/technological function faulted (17)
Reaction:
OFF1 (OFF2, OFF3)
Acknowledge:
IMMEDIATELY
Cause:
The difference between the position setpoint position actual value (following error dynamic model, r2563) is higher
than the tolerance (p2546).
- the drive torque or accelerating capacity exceeded.
- position measuring system fault.
- encoder cable interrupted.
- position control sense incorrect.
- mechanical system locked.
- excessively high traversing velocity or excessively high position reference value (setpoint) differences
Remedy:
Check the causes and resolve.
F07453
LR: Position actual value preprocessing error
Message class:
Application/technological function faulted (17)
Reaction:
OFF1 (OFF2, OFF3)
Acknowledge:
IMMEDIATELY
Cause:
An error has occurred during the position actual value preprocessing.
Remedy:
Check the encoder for the position actual value preprocessing.
See also: p2502 (LR encoder assignment)
A07454
LR: Position actual value preprocessing does not have a valid encoder
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Reaction:
NONE
Acknowledge:
NONE
Cause:
One of the following problems has occurred with the position actual value preprocessing:
- an encoder is not assigned for the position actual value preprocessing (p2502 = 0).
- an encoder is assigned, but no encoder data set (p0187 = 99 or p0188 = 99).
- an encoder an an encoder data set have been assigned, however, the encoder data set does not contain any
encoder data (p0400 = 0) or invalid data (e.g. p0408 = 0).
Remedy:
Check the drive data sets, encoder data sets and encoder assignment.
See also: p0187 (Encoder 1 encoder data set number), p0188 (Encoder 2 encoder data set number), p0400
(Encoder type selection), p2502 (LR encoder assignment)
A07455
EPOS: Maximum velocity limited
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Reaction:
NONE
Acknowledge:
NONE
Cause:
The maximum velocity (p2571) is too high to correctly calculate the modulo correction.
Within the sampling time for positioning (8 ms), with the maximum velocity, a maximum of the half modulo length
must be moved through. p2571 was limited to this value.
Remedy:
Reduce the maximum velocity (p2571).
1088
SINAMICS G120 CU250S-2 Control Units
List Manual, 09/2017, A5E33842890