12.4.13 Connecting to CC-Link module (MELSEC iQ-F Series) with Ver.1/Ver.2
compatibles mixed
This section describes the settings of the GOT and the CC-Link module (MELSEC iQ-F Series) with Ver.1/Ver.2 compatibles
mixed in the following system configuration.
■1. System configuration
■2. Module parameter setting of GX Works3
(1) [Module parameter] of GX Works3
(a)
Module parameter
Station type
Mode
Station No.
Transmission speed
Parameter setting
*1
12 - 78
12.4 PLC Side Setting
POINT
POINT
POINT
CC-Link module (MELSEC iQ-F Series)
For details of the CC-Link module (MELSEC iQ-F Series), refer to the following manual.
Manuals of MELSEC iQ-F Series
<CC-Link module>
(Use the default value for settings other than the following.)
Type : Master station
Station No. : Station No.0
Mode Setting : Remote net (Ver.2 mode)
All connect count : 2
Transmission speed : 156kbps
Item
*1
Adjust the settings with GOT settings.
<GOT(Ver.1 compatible)>
(Use the default value for
settings other than the following.)
Station type : Intelligent device station
Station No. : Station No.1
Number of stations occupied : Exclusive station 1
Transmission speed : 156kbps
<GOT(Ver.2 compatible)>
(Use the default value for
settings other than the following.)
Station type : Intelligent device station
Station No. : Station No.2
Expanded cyclic setting : Single
Number of stations occupied : Exclusive station 1
Transmission speed : 156kbps
Set value
Master station
Remote net (Ver.2 mode)
0 (fixed)
156kbps
Parameter
: Necessary
Setting necessity at GOT connection
×
: As necessary
: Not necessary