5.4.1
Connecting to MELSEC iQ-R Series built-in Ethernet port CPU (one-to
one connection)
This section describes the settings of the GOT and Built-in Ethernet port CPU in the following case of system configuration.
■1. GOT Side Communication format is UDP
(1) System configuration
For connecting one Built-in Ethernet port CPU to one GOT, the PLC side settings are not required. Set [Ethernet] for
[Controller Setting] on GT Designer3, and then connect Built-in Ethernet port CPU to the GOT.
(MELSEC iQ-R Series)
*1
For the settings when using system devices including a hub and a transceiver, refer to the following.
*2
These setting items do not exist at the PLC side. However, the virtual values must be set on the GOT side.
(2) [Controller Setting] and [Ethernet] of GT Designer3
(a)
Controller setting
GOT Net No.
GOT Station
GOT Standard Ethernet Setting
GOT Communication Port No.
Retry
Startup Time
Timeout Time
POINT
POINT
POINT
Built-in Ethernet port CPU
For details of Built-in Ethernet port CPU, refer to the following manual.
Manuals of MELSEC iQ-R Series
Manuals of MELSEC iQ-F Series
<Built-in Ethernet port CPU>
(Use the default value for settings
other than the following.)
Network No.
PLC No.
IP address
Port No.
Communication format :UDP (fixed)
5.4.7 Connecting to MELSEC-Q/L Series built-in Ethernet port CPU (multiple connection)
(2) [Controller Setting] and [Ethernet] of GT Designer3
POINT
POINT
POINT
(1) [Controller Setting] and [Ethernet] of GT Designer3
For [Controller Setting] and [Ethernet] of GT Designer3, refer to the following.
5.3.1 Setting communication interface (Controller Setting)
(2) Ethernet setting
When connecting Built-in Ethernet port RCPU to a GOT, the setting items for the network No.
and station No. do not exist at the PLC side. However, these virtual values must be set on the
GOT side. Therefore, set the network No. and station No.
Set the network No. that does not exist on the network system and any station No.
Item
<GOT>
(Use the default value for settings
other than the following.)
Network No.
:1
PLC No.
:1
IP address
:192.168.3.18
Port No.
:5001
Communication format :UDP (fixed)
*1
*2
:1 (virtual)
*2
:2 (virtual)
:192.168.3.39
:5006 (fixed)
Set value (Use default value)
192.168.3.18
5001
3times
3sec
3sec
5.4 PLC Side Setting
1
1
5 - 29
5