Communication Detail Settings - Mitsubishi Electric GOT2000 Series Connection Manual

Graphic operation terminal
Hide thumbs Also See for GOT2000 Series:
Table of Contents

Advertisement

10.3.2

Communication detail settings

Make the settings according to the usage environment.
Item
Set the network Type
*4
Network Type
(Default: CC IE Control)
Set the network No.
Network No.
(Default: 1)
Set the station No. of the GOT.
Station No.
(Default: 1)
Group No.
-
Set the operation mode of the GOT.
Mode Setting
(Default:
Online (auto. reconnection))
Transmission Speed
-
Set the number of refreshes to secure the send/receive data in station units
during communication.
Refresh Interval
(Default: 1ms)
Valid when [Block data assurance per station is available.] is checked by the
control station side network parameters of the CC-Link IE Controller Network.
Set the number of retries to be performed when a communication timeout
occurs.
Retry
When no response is received after retries, a communication times out.
(Default: 3times)
Set the time period for a communication to time out.
Timeout Time
(Default: 3sec)
Set the delay time for reducing the load of the network/destination PLC.
Delay Time
(Default: 0ms)
Set the monitor speed for the CC-Link IE controller network.
*5
This setting is not valid in all systems.
Monitor Speed
(Default: High)
Set the servo axis switching GD device head No.
(Default: 10)
Servo axis switching GD
For details, refer to the following POINT.
device head No.
*1
For details, refer to the following manual.
CC-Link IE Controller Network Reference Manual
*2
This range is effective when collecting a large amount of data (such as logging and recipe function) on other than the monitor
screen.
However, the range may affect the sequence scan time when connecting to Q00UJ/Q00U/Q01U/Q02UCPU or Q00J/Q00/
Q01CPU.
If you want to avoid the influence on the sequence scan time, do not set [High(Normal)].
(This setting hardly affects QCPUs other than the above.)
*3
Set this item if you want to avoid the influence on the sequence scan time further than the [Middle] setting when connecting to
Q00UJ/Q00U/Q01U/Q02UCPU or Q00J/Q00/Q01CPU.
However, the monitor speed may be reduced.
Description
(5) Indirect specification of the servo axis No.
Range
• CC IE Control
• CC IE Control extended mode
1 to 239
1 to 120
0 (fixed)
• Online (auto. reconnection)
• Offline
*1
• Test station
*1
• Self-loopback test
*1
• Internal self-loopback test
*1
• Line test
*1
• H/W test
1 Gbps (fixed)
1 to 1000ms
0 to 5times
1 to 90sec
0 to 300ms
*2
*3
High(Norton)
/Middle/Low
0 to 65520
10.3 GOT side settings
10
10 - 11

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents