Mitsubishi Electric GOT2000 Series Connection Manual page 706

Graphic operation terminal
Hide thumbs Also See for GOT2000 Series:
Table of Contents

Advertisement

(3) Transmission speed setting switch
Transmission speed setting
switch
B RATE
0 156K
1 625K
2 2. 5M
3 5M
4 10M
*1
(4) Condition setting switches
Condition setting switches
SW OFF
1
2
3
4
5
6
7
8
*1
12 - 64
12.4 PLC Side Setting
Transmission speed setting (156kbps)
Specify the same transmission speed as that of the GOT.
Setting switch
SW1
SW2
SW3
ON
M / L
S. M
SW4
CLR
HLD
1/2
3/4
1/4
2/3
SW5
ISM SFM
SW6
SW7
SW8
Will be valid when the CC-Link module is a local station.
In the case of the master station, turn off it.
POINT
POINT
POINT
When the switch setting has been changed
Turn the PLC CPU OFF then ON again, or reset the PLC CPU.
Description
*1
: Necessary
Description
Station type
(Master station/Local
station)
Not used
Input data status of the data
link error station
(clear)
Number of stations
*1
occupied
Not used
Module mode
(Intelligent mode)
: Necessary
Setting necessity at GOT
Set value
connection
0
: As necessary
Setting necessity at GOT
Set value
OFF
(fixed)
OFF
(fixed)
OFF
OFF
(fixed)
OFF
(fixed)
OFF
(fixed)
: As necessary
: Not necessary
connection
: Not necessary