Mitsubishi Electric GOT2000 Series Connection Manual page 346

Graphic operation terminal
Hide thumbs Also See for GOT2000 Series:
Table of Contents

Advertisement

(c)
Buffer memory settings used in the present example
Buffer memory address
Dec (Hex)
0 to 1 (0 to 1H)
(19 to 1AH)
*1
5 - 80
5.4 PLC Side Setting
IP address of Ethernet module
16 (10H)
Application setting
24 (18H)
Port No. of Ethernet module
25 to 26
IP address of GOT
27 (1BH)
Port No. of GOT
80 (50H)
Initial fault code
The details of the application setting are shown below.
Settings 1), 2) and 3) can be changed by the user.
4), 5) and 6) are fixed.
b15
b14
b13
b12
b11
0
0
0
0
0
6)
1)
Fixed buffer application
0: For sending; no exchange
1: For receiving
2)
Existence check
0: No
1: Yes
3)
Pairing open
0: No
1: Yes
4)
Communication format (Set to "1" (UDP/IP).)
0: TCP/IP
1: UDP/IP
5)
Fixed buffer exchange (Set to "0" (With procedure).)
0: With procedure
1: Without procedure
6)
Open method (Set to "00" (Active, UDP/IP).
00: Active, UDP/IP
10: Unpassive
11: Fullpassive
Item
*1
b10
b9
b8
b7
b6
b5
b4
0
0
1
0
0
0
0
5)
4)
3)
b3
b2
b1
b0
0
0
0
0
2)
1)
Set value
C0A80313H
(192.168.3.19)
100H
5001
FFFFFFFFH
FFFFH (fixed)