(2) System configuration example 2
In the multiple CPU configuration, the GOT cannot access the CPU module on the other network via the CPU No.
("MELSOFT Connection Extended Setting": "Use") and relaying the network module that is controlled by the other
CPU No. ("MELSOFT Connection Extended Setting": "Not use" or "MELSOFT Connection Extended Setting" is not
supported).
(a)
System configuration figure
"Ethernet setting"
Port No. of the connected equipment:
[5001]
1) Counter measures
Take one of the following counter measures.
• Change "MELSOFT Connection Extended Setting" at the PLC side.
Set "MELSOFT Connection Extended Setting" to "Use" in the CPU module No. 2 whose "MELSOFT
Connection Extended Setting" is available.
• Change "Ethernet setting" at the GOT side.
Set the port No. of the connected equipment to [5006] by "Ethernet setting" at the GOT side.
5 - 106
5.5 Precautions
"MELSOFT Connection Extended Setting": "Not use"
"MELSOFT Connection Extended Setting": "Use"
GOT
Ethernet
QnUCPU User's Manual (Communication via Built-in Ethernet Port)
5.3.4 Ethernet setting
Ethernet module that
the CPU No. 2 controls
CPU
CPU
Ethernet
module
module
module
No. 1
No. 2
CPU
module
Ethernet