Mitsubishi Electric GOT2000 Series Connection Manual page 330

Graphic operation terminal
Hide thumbs Also See for GOT2000 Series:
Table of Contents

Advertisement

■1. System configuration (for Q series)
*1
■2. [Network parameter] of GX Developer
(1) Network parameter
Network type
*1
Starting I/O No.
*2
Network No.
Group No.
*3
Station No.
Mode
Operation setting
5 - 64
5.4 PLC Side Setting
The Ethernet module is mounted on the base unit slot 0.
The Start I/O No. of the Ethernet module is set to "0".
POINT
POINT
POINT
When connecting to Q170MCPU
When connected to Q170MCPU, the start I/O No. of the Ethernet module is set to "70".
Item
<GOT> (The settings other than the
following are set to the default)
Network No.
PLC No.
IP address
Port No.
Communication format : UDP (fixed)
*1
<Ethernet module> (The settings other than the
following are set to the default)
Network No.
: 1
PLC No.
: 2
IP address
: 192.168.3.19
Port No.
: 5001
Communication format
: UDP(fixed)
Set value
Ethernet (fixed)
0000H
1
0 (fixed)
2
Online (fixed)
Refer to (2)
: 1
: 1
: 192.168.3.18
: 5001
Setting necessity at GOT
connection