■2. Precautions when preparing a cable
(1) Cable
Use a shielded twisted pair cable of 0.3mm2 or more as a cable for GOT multi-drop connection.The following shows
recommended model names and manufacturers of the cable to be used.
Manufacturer
Mitsubishi Electric Cable Industries,Ltd
Showa Electric Wire & Cable Co.,Ltd
Sumitomo Electric Industries.,Ltd
The Furukawa Electric Co.,Ltd
Fujikura Ltd.
Two-pair cable structural
drawing example
(2) Cable for converting D-sub9 pin connector to terminal block
Create by yourself, referring to the following connection diagram.
Make sure to connect the wiring branched on the GOT side connector.
(3) GOT side connector
For the GOT side connector, refer to the following.
1.4.1 GOT connector specifications
SPEV(SB)-0.5-2P
KMPEV-SB
CWS-178 0.5SQ
DPEV SB 0.3
DPEV SB 0.5
D-KPEV-SB 0.5
IPEV-SB 2P
IPEV-SB 2P
Pair
Shield
Example of connection diagram for 2 pair wiring
SDA1
SDB1
RDA1
RDB1
SDA2
SDB2
RDA2
RDB2
SG
FG
Use a shielded twisted pair cable of 0.2mm
Use an applicable cable to D-sub connector.
Wiring should be the shortest distance.
Model
2P
3P
3P
3P
0.3 mm2
0.5 mm2
Three-pair cable structural
drawing example
1
SDA
6
SDB
2
RDA
7
RDB
5
SG
3
RSA
8
RSB
4
CSA
9
CSB
Shell
FG
2
or more.
19.4 Connection Diagram
Remark
Two-pair cable of 0.5mm2
Two-pair cable of 0.5mm2
Three-pair cable of 0.3mm2
Three-pair cable of 0.5mm2
Three-pair cable of 0.5mm2
Two-pair cable of 0.3mm2
Two-pair cable of 0.5mm2
19 - 25