Mitsubishi Electric GOT2000 Series Connection Manual page 591

Graphic operation terminal
Hide thumbs Also See for GOT2000 Series:
Table of Contents

Advertisement

(a) Caution immediately after the GOT setup
When a servo amplifier device where indirect specification (100 to 115) of the servo axis
No. is monitored on the initial display screen, "out of device range" may occur. In that
case, set the indirect specification device value before monitoring on the screen.
(b) Caution for multi-channel connection (axis No. indirect specification)
For multi-channel connection, when the head No. of the servo axis switching GD device
is used and the setting range is duplicated, the axis No. of the servo amplifier device that
is set to each channel switches simultaneously.
(c) Caution for multi-channel connection (station No. indirect specification and axis No.
indirect specification)
For multi-channel connection, when station No. indirect specification (GD10 to GD25) is
used with a inverter or third party temperature controller and the head No. of the servo
axis switching GD device is set to "10" in other channel, the axis No. of the servo
amplifier and station No. of the inverter or third party temperature controller which are set
to each channel switch simultaneously.
10.3 GOT side settings
10
10 - 13

Hide quick links: