(3) System configuration example 3
(a)
System configuration figure-1
In the system configuration where the Ethernet module is mounted on the same CPU base, when the network
Nos. of the CPU built-in Ethernet port and Ethernet module are duplicated, the GOT cannot access the other
CPU No. in the multiple configuration via the CPU built-in Ethernet port ("MELSOFT Connection Extended
Setting" to "Use").
1
N/W No.:
Station No.: 1
IP address: 192.168.3.39
"MELSOFT Connection Extended Setting": "Use"
1) Counter measures
Take one of the following counter measures.
• Change "Ethernet setting" at the GOT side.
Set the port No. of the connected equipment to [5006] by "Ethernet setting" at the GOT side.
5.3.4 Ethernet setting
• Change the connection route
Connect the GOT to the CPU module No. 2 via the Ethernet module.
The network No. is duplicated.
CPU
Ethernet
CPU
module
module
module
No. 1
No. 2
CPU
CPU
module
module
No. 1
No. 2
Ethernet
1
N/W No.:
Station No.: 10
IP address: 192.168.3.10
GOT
Ethernet
Ethernet
module
GOT
"Ethernet setting"
Port No. of the connected equipment:
[5001]
5 - 107
5.5 Precautions