Mitsubishi Electric GOT2000 Series Connection Manual page 794

Graphic operation terminal
Hide thumbs Also See for GOT2000 Series:
Table of Contents

Advertisement

■10. Connecting FREQROL-A700 series
Make the communication settings of the inverter.
Be sure to perform the inverter reset after updating each parameter.
(1) Communication port and corresponding parameters
GOT connection destination
PU connector
RS-485 terminal
(2) Communication settings of inverter
Set the following parameters using the PU (parameter unit).
Do not change these parameters, even though they can be monitored from the GOT. If they are changed,
communication with the GOT is disabled.
Setting item
PU communication station number/
RS-485 communication station number
PU communication speed/
RS-485 communication speed
PU communication stop bit length/
RS-485 communication stop bit length
PU communication parity check/
RS-485 communication parity check
Number of PU communication retries/
RS-485 communication retry count
PU communication check time interval/
RS-485 communication check time interval
PU communication waiting time setting/
RS-485 communication waiting time setting
PU communication CR/LF selection/
RS-485 communication CR/LF selection
Protocol selection
Operation mode selection
Communication startup mode selection
Communication EEPROM write selection
*1
*2
*3
*4
14 - 38
14.2 System Configuration
*1
PU connector
*2
*2
*2
Setting items are parameter names described in the manual of FREQROL-A700 series.
Settings on the GOT can be changed.
When changing the settings on the GOT, be sure to change the parameters on the inverter to correspond with the GOT settings.
Inverter default values (No need to change)
Since the value has been set as a default, no setting is required when connecting to the PU connector on the inverter side.
POINT
POINT
POINT
(1) Automatic setting with Pr.999
If Pr.999 is set as the following, the communication settings other than [PU communication
station number] and [Communication EEPROM write selection] can be automatically set in a
batch to the default communication settings of the GOT side.
Parameter No.
*1
Pr.999
*1
When monitoring the value of Pr.999, 9999 is always monitored.
(2) Inverters available for automatic batch setting
Parameters are not automatically set in a batch depending on the SERIAL (production
number) symbol of the inverter to be used. For details, contact your local distributor.
Parameters corresponding to inverter
Pr.79, Pr.117 to Pr.124, Pr.340, Pr.342
Pr.79, Pr.331 to Pr.337, Pr.340 to Pr.342, Pr.549
Parameter No.
RS-485
Pr.117
Pr.331
Pr.118
Pr.332
Pr.119
Pr.333
Pr.120
Pr.334
Pr.121
Pr.335
Pr.122
Pr.336
Pr.123
Pr.337
Pr.124
Pr.341
-
Pr.549
PU connector
Pr.79
PU connector
Pr.340
Pr.342
Set value
Description
10
GOT Initial settings (PU connector)
11
GOT Initial settings (RS-485)
Set value
Contents of setting
0 to 31
14.2.9 Station number setting
*4
192
10
Stop bit length: 1bit
1
The inverter will not come to an alarm
9999
*4
Communication check suspension
9999
0
*3
With CR, without LF
1
*3
Mitsubishi Electric inverter protocol
0
1
PU operation mode
*3
RS-485
External operation mode at power on
0
*3
Refer to Pr.79 settings.
0
RS-485
1
Network operation mode.
*3
Written to RAM and EEPROM
0
Operation in parameter setting mode
[AUTO]
19200bps
Data length: 7bit
Odd
stop.
0ms
[GOT]
[1]Write
-