Connecting To Cc-Link Module (Melsec Iq-R Series) With Ver.1/Ver.2 Compatibles Mixed - Mitsubishi Electric GOT2000 Series Connection Manual

Graphic operation terminal
Hide thumbs Also See for GOT2000 Series:
Table of Contents

Advertisement

12.4.3
Connecting to CC-Link module (MELSEC iQ-R Series) with Ver.1/Ver.2
compatibles mixed
This section describes the setting of the GOT and CC-Link module (MELSEC iQ-R Series) with Ver.1/Ver.2 compatibles
mixed in the following system configuration.
■1. System configuration
*1
The CC-Link module is mounted on the base unit slot 0.
The Start I/O No. of the CC-Link module is set to "0".
■2. Module parameter setting of GX Works3
(1) [Module parameter] of GX Works3
(a)
Module parameter
Station type
Mode
Station No.
Transmission speed
Parameter setting
*1
Adjust the settings with GOT settings.
POINT
POINT
POINT
CC-Link module (MELSEC iQ-R Series)
For details of the CC-Link module (MELSEC iQ-R Series), refer to the following manual.
Manuals of MELSEC iQ-R Series
*1
<CC-Link module>
(Use the default value for settings other than the following.)
Type
: Master station
Station No.
: Station No.0
Mode Setting
: Remote net (Ver.2 mode)
All connect count
: 2
Transmission speed
: 156kbps
Item
*1
<GOT(Ver.1 compatible)>
(Use the default value for
settings other than the following.)
Station type
: Intelligent
device station
Station No.
: Station No.1
Number of
:
Exclusive station 1
stations occupied
Transmission speed
:
156kbps
<GOT(Ver.2 compatible)>
(Use the default value for
settings other than the following.)
Station type
: Intelligent
device station
Station No.
: Station No.2
Expanded cyclic
Single
:
setting
:
Number of
Exclusive
stations occupied
station 1
Transmission speed :
156kbps
Set value
Master station
Remote net (Ver.2 mode)
0 (fixed)
156kbps
Parameter
: Necessary
12.4 PLC Side Setting
Setting necessity at GOT connection
: As necessary
: Not necessary
12 - 23
12

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents