19.5.2

Communication detail settings

Make the settings according to the usage environment.
Item
Transmission Speed
Retry
Timeout Time
GOT Address
Delay Time
19 - 28
19.5 GOT Side Settings
Set this item when change the transmission speed used for communication
with the connected equipment. (Default: 115200bps)
Set the number of retries to be performed when a communication timeout
occurs.
When receiving no response after retries, the communication times out.
(Default: 0time)
Set the time period for a communication to time out. (Default: 3sec)
Specify the station number of the host station in the system configuration.
(Default: 0)
Set this item to adjust the transmission timing of the communication request
from the GOT. (Default: 0ms)
POINT
POINT
POINT
(1) Communication interface setting by Utility
The communication interface setting can be changed on the Utility's [Communication
Settings] after writing [Controller Setting] of project data.
For details on the Utility, refer to the following manual.
GOT2000 Series User's Manual (Utility)
(2) Precedence in communication settings
When settings are made by GT Designer3 or the Utility, the latest setting is effective.
Description
Range
4800bps,
9600bps,
19200bps,
38400bps,
57600bps,
115200bps
0 to 5times
1 to 30sec
0 to 15
0 to 300 ms