(b)
System configuration figure-2
When the network Nos. of the CPU built-in Ethernet port and Ethernet module are duplicated in the following
system configuration, the CPU module cannot access to the GOT via the CPU built-in Ethernet port ("MELSOFT
Connection Extended Setting": "Use") using GT Designer3.
1
N/W No.:
Station No.: 1
IP address: 192.168.3.39
"MELSOFT Connection Extended Setting": "Use"
1) Counter measures
Take one of the following counter measures.
• Change the connection route.
Connect the GOT to the CPU module No. 2 via the Ethernet module.
5 - 108
5.5 Precautions
The network No. is duplicated.
CPU
Ethernet
module
module
USB connection
USB connection
1
N/W No.:
Station No.: 10
IP address: 192.168.3.10
Ethernet
CPU
Ethernet
module
module
Ethernet
"Ethernet setting"
Port No. of the connected equipment:
GOT
[5001]
GOT