Mitsubishi Electric GOT2000 Series Connection Manual page 710

Graphic operation terminal
Hide thumbs Also See for GOT2000 Series:
Table of Contents

Advertisement

(2) Program condition (for FROM/TO instruction)
This program writes parameters to the buffer memory when PLC CPU status changes from STOP to RUN and
automatically starts the data link with FROM/TO instruction.
(a)
I/O signal of CC-Link module
(b)
Devices used by user
M100, M101
M102, M103
(c)
Buffer memory settings used in the present example
Buffer memory
Decimal (Hex)
*1
12 - 68
12.4 PLC Side Setting
Control & Communication Link System Master/Local Module Type AJ61BT11/A1SJ61BT11
User's Manual
Device
Flag for parameter setting
Flag for data link startup
D0
Number of connected modules
D1
Number of retry
D2
Automatic reconnection station count
D3
Operation specification in the case of CPU failure
D4
Reserved station specification (Station No. 1 to Station No. 16)
D5
Error invalid station specification (Station No. 1 to Station No. 16)
D6
Station data (first module)
D400
Error code in the case of data link startup failure
address
1 (1H)
Number of connected modules
2 (2H)
Number of retry
3 (3H)
Automatic reconnection station count
6 (6H)
Operation specification in the case of CPU failure
16 (10H)
Reserved station specification (Station No. 1 to Station No. 16)
Error invalid station specification
20 (14H)
(Station No. 1 to Station No. 16)
32 (20H)
Station data (first module)
Details for the station data are shown below.
For 1) and 2), set the same station No. and number of station occupied settings as those of the GOT.
For 3), the setting is fixed.
b15
to
b12
b11
3)
1) Station No. (Set the same station No. as that of the GOT.)
01H to 40H: Station No. 1 to Station No. 64
2) Number of stations occupied (Set the same setting of the number of station occupied as that of the GOT.)
1H: Exclusive station 1
2H: Exclusive station 2
3H: Exclusive station 3
4H: Exclusive station 4
3) Station type (2H: Set it to intelligent device station.)
0H: Remote I/O station
1H: Remote device station
2H: Intelligent device station (Incl. local station)
Item
*1
to
b8
b7
to
2)
1)
Application
0 (No specification)
0 (No specification)
b0
Set value
1 (1 module)
3 (3times)
1 (1 station)
0 (stop)
2101H