Mitsubishi Electric GOT2000 Series Connection Manual page 1123

Graphic operation terminal
Hide thumbs Also See for GOT2000 Series:
Table of Contents

Advertisement

Step 4.
Double-click [GOT] of the PLC side I/F to display [PLC side I/F Detailed Setting of GOT].
Step 5.
Check-mark [CC IE Cont] in [Detail setting for GOT and PLC connection].
Step 6.
Set the [CPU mode] and [Relay network No.] and [Relay station No.].
• When the target PLC has the same network No. as that of the GOT
Set the number assigned to the PLC that is targeted by using the transparent function and CC-Link IE
controller network module.
• When the target PLC has a different network No. from that of the GOT
Set the number assigned the PLC that is used as a relay station and CC-Link IE controller network
module.
Step 7.
Return [Transfer Setup], click [Other Station (Single Network)], and double-click [CC IE Cont NET/10(H)].
Step 8.
Set as shown below and click [OK].
• When the GOT and PLC are on the same network
Select [Access to CC IE Cont module set on PLC side I/F].
• When the GOT and PLC are on the different networks
Select [Other station in the same loop or access to multilevel system] and set [Network No.] and [Station
No.].
Step 9.
The screen returns to the [Connection Channel Setup]. Click [Connection Test] to check if GX Works3 has
been connected to the RCPU.
MELSOFT GX Works3
22.7 Personal Computer Side Setting
22
22 - 67