7.2.7
Connecting to CPU port/D-sub
9-pin conversion cable, SIO
port adapter cable
Setting of PLC CPU
Make the PLC CPU settings, displaying [Configuration]
[Communication Settings] with the program
development tool or the ladder-programming tool.
Item
Set the communication mode of the CPU (transmission
speed and data format).
Set the transmission speed and data format according to
settings of the transmission speed, data length, parity
and stop bit on the GOT side.
For details on these GOT side settings, refer to the
following.
7.2.5Setting communication interface
(Communication settings)
Item
Communication
mode 0
Communication
Communication
mode 1
*1
mode
Communication
mode 2
Communication
mode 3
Communication
mode 4
Communication
mode 5
Communication
mode 6
Communication
mode 7
Communication
mode 8
Communication
mode 9
Set the following when using the CPU programming port
as the PC link function.
Make the checksum setting according to the sum check
setting on the GOT side.
For the sum check setting on the GOT side, refer to the
following.
7.2.5 ■ Setting communication interface
CPU PC link
(Communication settings)
function
settings
Item
Use of PC link function
Checksum
End character
Protect function
*1
The communication mode that can be selected differs
according to the CPU.
7 - 10
7. CONNECTION TO YOKOGAWA PLC
7.2 Serial Connection
Set value
Transmission speed and data format
Transmis
sion
Data bit
Parity
speed
9600
8bits
Even
1bit
bps
9600
8bits
None
1bit
bps
19200
8bits
Even
1bit
bps
19200
8bits
None
1bit
bps
38400
8bits
Even
1bit
bps
38400
8bits
None
1bit
bps
57600
8bits
Even
1bit
bps
57600
8bits
None
1bit
bps
115200
8bits
Even
1bit
bps
115200
8bits
None
1bit
bps
Set value
Mark. (Use enabled)
Mark. (ON)
Do not mark. (OFF)
Do not mark. (OFF)
Do not mark. (OFF)
7.2.8
Switch setting on the PC link module
Set the switches accordingly.
POINT
POINT
POINT
Switch setting
Set the switches before mounting the Ethernet Interface
Module on the base unit.
F3LC01-1N
F3LC11-1N
Stop
bit
(1) Transmission speed setting switch
Set the same transmission speed of the GOT.
For the transmission speed setting on the GOT side,
refer to the following.
7.2.5 ■ Communication detail settings
7 8
9
6
0
5
4
1
3
2
Connecting PC link module
(F3LC01-1N, F3LC11-1N,
F3LC11-2N, F3LC11-2F)
F3LC11-2N
F3LC11-2F
STATION
NO.
(3)
Side view indicated by A
(For the F3LC01-1N,
F3LC11-1N, F3LC11-2N)
TERMINATOR
(4)
2-
4-WIRE
With right side cover
OFF
SD A
removed
SD B
RD A
A
A
SD B
SG
SHIELD
Side view indicated by A
(For the F3LC11-2F)
With right side cover
removed
*1
Transmission speed
Setting
4
5
6
*1Only transmission speeds available on the GOT side
are shown.
(1)
1
O
2
F
F
3
(2)
4
5
6
7
8
(1)
1
1
O
O
F
2
F
2
F
3
F
3
(2)
4
4
5
5
6
6
7
7
8
8
(5)
4800bps
9600bps
19200bps

Advertisement

Table of Contents
loading

Table of Contents