Mitsubishi Electric GOT2000 Series Connection Manual page 943

Graphic operation terminal
Hide thumbs Also See for GOT2000 Series:
Table of Contents

Advertisement

■4. Ethernet(MITSUBISHI ELECTRIC), Gateway
Item
GOT Net No.
*1
GOT Station
GOT Communication Port No.
Retry
Startup Time
Timeout Time
Delay Time
Servo axis switching GD device
head No.
*1
Each of [GOT Station] set in the communication detail setting and [Station] set in the Ethernet setting must be set to different
station numbers.
Set the network No. of the GOT. (Default: 1)
Set the station No. of the GOT. (Default: 18)
Set the GOT port No. for the connection with the Ethernet module.
(Default: 5001)
Set the number of retries to be performed when a communication
timeout occurs.
When receiving no response after retries, the communication times out.
(Default: 3times)
Specify the time period from the GOT startup until GOT starts the
communication with the PLC CPU. (Default: 3sec)
Set the time period for a communication to time out. (Default: 3sec)
Set the delay time for reducing the load of the network/destination PLC.
(Default: 0ms)
Set the servo axis switching GD device head No.
(Default: 10)
17.4.4 Ethernet setting
POINT
POINT
POINT
(1) Communication interface setting by Utility
The communication interface setting can be changed on the Utility's [Communication
Settings] after writing [Controller Setting] of project data.
For details on the Utility, refer to the following manual.
GOT2000 Series User's Manual (Utility)
(2) Precedence in communication settings
When settings are made by GT Designer3 or the Utility, the latest setting is effective.
Description
17.4 GOT Side Settings
Range
1 to 239
1 to 64
1024 to 5010 to 5014 to 65534
(Except for 5011, 5012, 5013 and
49153 to 49170)
0 to 5times
3 to 255sec
3 to 90sec
0 to 10000 (
10ms)
<For GT27, GT25, GT23>
0 to 65520
<For GT21, GS>
0 to 2032
17 - 13