(4) Communication settings of inverter (Manual setting)
Set the following parameters using the PU (operation panel or parameter unit). Before setting the parameters, set
Pr.160 (User group read selection) to 0 so that simple mode + extended parameters are displayed. (The default value
of FREQROL-F800 is 9999.)
Do not change these parameters, even though they can be monitored from the GOT. If they are changed,
communication with the GOT is disabled.
Setting item
PU communication station number/
RS-485 communication station number
PU communication speed/
RS-485 communication speed
PU communication stop bit length/data length/
RS-485 communication stop bit length/data length
PU communication parity check/
RS-485 communication parity check
Number of PU communication retries/
RS-485 communication retry count
PU communication check time interval/
RS-485 communication check time interval
PU communication waiting time setting/
RS-485 communication waiting time setting
PU communication CR/LF selection/
RS-485 communication CR/LF selection
Protocol selection
Operation mode selection
Communication startup mode selection
Communication EEPROM write selection
PLC function operation selection
*1
Setting items are parameter names described in the manual of FREQROL-A800, F800 series.
*2
Settings on the GOT can be changed.
When changing the settings on the GOT, be sure to change the parameters on the inverter to correspond with the GOT settings.
*3
Since the value has been set as a default, no setting is required when connecting to the PU connector on the inverter side.
*4
To use the FREQROL 800 driver, set 0.
*5
Inverter default values (No need to change).
*6
The inverter side setting defaults to 0 (invalid).
To use the PLC function, set 1 or 2.
Operation mode selection
RS-485 communication speed
RS-485 communication stop bit length
RS-485 communication parity check
RS-485 communication retry count
RS-485 communication check time interval
RS-485 communication waiting time setting
Communication startup mode selection
RS-485 communication CR/LF selection
PLC function operation selection
Parameter No.
*1
PU connector
Pr.117
Pr.118
*2
Pr.119
*2
Pr.120
*2
Pr.121
Pr.122
Pr.123
Pr.124
-
Pr.79
Pr.340
Pr.342
*6
Pr.414
Setting item
Protocol selection
Set value
RS-485
Pr.331
0 to 31
*3
Pr.332
192
*4
Pr.333
10
Pr.334
1
Pr.335
9999
*3
Pr.336
9999
Pr.337
0
*5
Pr.341
1
*5
Pr.549
0
PU connector
RS-485
PU connector
RS-485
*5
0
1, 2
14.2 System Configuration
Set value
0
1152
0
1
9999
9999
0ms
1
1
*1
2
0
Contents of setting
14.2.9 Station number setting
19200bps
Data length: 7bit
Stop bit length: 1bit
Odd
The inverter will not come to an
alarm stop.
Communication check suspension
0ms
With CR, without LF
Mitsubishi Electric inverter protocol
1
PU operation mode
External operation mode at power
*5
0
on
*5
Refer to Pr.79 settings.
0
1
Network operation mode.
Written to RAM and EEPROM
Enabled with 1 and 2.
14 - 41