Connecting To Cc-Link Module (Qna Series) - Mitsubishi Electric GOT2000 Series Connection Manual

Graphic operation terminal
Hide thumbs Also See for GOT2000 Series:
Table of Contents

Advertisement

12.4.10 Connecting to CC-Link module (QnA Series)

This section describes the settings of the GOT and CC-Link module (QnA Series) in the following case of system
configuration.
■1. System configuration
*1
12 - 54
12.4 PLC Side Setting
POINT
POINT
POINT
CC-Link module (QnA Series)
For details of the CC-Link module (QnA Series), refer to the following manual.
Control & Communication Link System Master/Local Module Type AJ61QBT11/
A1SJ61QBT11 User's Manual
<CC-Link module>
*1
(Use the default value for settings other than the following.)
Station type
: Master station
: Station No.0
Station No.
Mode setting
: Remote net mode
All connect count
: 1
Transmission speed : 156kbps
The CC-Link module is mounted on the base unit slot 0.
The Start I/O No. of the CC-Link module is set to "0"
<GOT> (Use the default value for settings other
than the following.)
Station type
: Intelligent device
station
Station No.
: Station No.1
Number of stations occupied : Exclusive station 1
Transmission speed
: 156kbps

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents