Mitsubishi Electric GOT2000 Series Connection Manual page 701

Graphic operation terminal
Hide thumbs Also See for GOT2000 Series:
Table of Contents

Advertisement

(c)
Buffer memory settings used in the present example
Buffer memory address
Decimal (Hex)
1(11 (1H)
2(22 (2H)
3(33 (3H)
6(66 (6H)
16(1016 (10H)
20(1420 (14H)
32(2032 (20H)
*1
Details for the station data are shown below.
For 1) and 2), set the same station No. and number of station occupied as those of the GOT.
For 3), the setting is fixed.
b15
1) Station No. (Set the same station No. as that of the GOT)
2) Number of stations occupied (Set the number of station occupied as that of the GOT)
3) Station type (2H: Set it to intelligent device station)
Number of connected modules
Number of retry
Automatic reconnection station count
Operation specification in the case of CPU failure
Reserved station specification (Station No. 1 to Station No. 16)
Error invalid station specification
(Station No. 1 to Station No. 16)
Station data (first module)
b12 b11
b8 b7
to
to
3)
2)
01H to 40H: Station No. 1 to Station No. 64
1H: Exclusive station 1
2H: Exclusive station 2
3H: Exclusive station 3
4H: Exclusive station 4
0H: Remote I/O station
1H: Remote device station
2H: Intelligent device station (Incl. local station)
Item
*1
to
b0
1)
12.4 PLC Side Setting
Set value
1 (1 module)
3 (3times)
1 (1 station)
0 (stop)
0 (No specification)
0 (No specification)
2101H
12
12 - 59