12.4.8
Connecting to MELSEC-L series with CC-Link Ver.1 compatible
This section describes the settings of the GOT and MELSEC-L in the following case of the system configuration.
■1. System configuration
(Example when using CC-Link module (L Series))
12 - 48
12.4 PLC Side Setting
POINT
POINT
POINT
(1) CC-Link module (L Series)
For details of the CC-Link module (L Series), refer to the following manual.
➠
MELSEC-L CC-Link System Master/Local Module User's Manual
(2) CC-Link function built-in CPU
For details on the CC-Link function built-in CPU, refer to the following manual.
➠
MELSEC-L CC-Link System Master/Local Module User's Manual
*1
<CC-Link module>
(Use the default value for the settings other than the following.)
Type
: Master station
Station No.
: Station No.0
Mode
: Remote net (Ver.1 mode)
All connect count
: 1
Transmission speed : 156kbps
<GOT>
(Use the default value for settings other
than the following.)
Station No.
: Station No.1
Expanded cyclic setting : Single
Number of
: Exclusive station 1
stations occupied
Transmission speed
: 156kbps