Confirming The Communication State On The Got Side (For Ethernet Connection) - Mitsubishi Electric GOT2000 Series Connection Manual

Graphic operation terminal
Hide thumbs Also See for GOT2000 Series:
Table of Contents

Advertisement

1.6.2
Confirming the communication state on the GOT side (For Ethernet
connection)
■1. Confirming the communication state on Windows, GT Designer3
(1) When using the Command Prompt of Windows
Execute a Ping command at the Command Prompt of Windows.
(a)
When normal communication
C:\>Ping 192.168.3.18
Reply from 192.168.3.18: bytes=32 time<1ms TTL=64
(b)
When abnormal communication
C:\>Ping 192.168.3.18
Request timed out.
(2) When using the [Test] of GT Designer3
Select [Communication] → [Communication settings] from the menu to display [TEST].
Step 1.
Set the [PC side I/F] to the [Ethernet].
Step 2.
Specify the [GOT IP Address] of the [Communication Configuration] and click the [Test] button.
Step 3.
Check if GT Designer3 has been connected to the GOT.
(3) When abnormal communication
At abnormal communication, check the followings and execute the Ping command or [Test] again.
• Mounting condition of Ethernet communication unit
• Cable connecting condition
• Confirmation of [Communication Settings]
• IP address of GOT specified by Ping command
1 - 44
1.6 Checking for Normal Monitoring