2) [I/O Assignment]
Set [I/O Assignment] in [System parameter].
At [I/O Assignment], assign Ethernet module (RJ71EN71 (E+E) in the following example).
3) [CPU Parameter]
Set the network number and station number of RJ72GF15-T2.
(1) In the system configuration example, the values are as follows.
Network No.: 1
Station No.: 2
4) Setting of Ethernet module
Set the IP address, Network No., and station number to the port communicating with the GOT in the Ethernet
module.
When setting the IP address, Network No., and station number in a batch
Set [Communications by Network No./Station No.] to [Enable] and [Setting Method] to [Use IP Address] so
that the third octet of IP address is the network number and the fourth octet is the station number.
(1) In the system configuration example, the network number is 2, and the station number is 1, so the value is
as follows.
IP Address: 192.168.2.1
4 - 26