Connecting To F3Sp66, F3Sp67, F3Sp71-4N (Built-In Ethernet Interface) - Mitsubishi Electric GOT2000 Series Connection Manual

Graphic operation terminal
Hide thumbs Also See for GOT2000 Series:
Table of Contents

Advertisement

7.3.6
Connecting to F3SP66,
F3SP67, F3SP71-4N (built-in
Ethernet interface)
Project setting/configuration setting
Set the setting with software for programming
apparatus.
Item
Set value
0.0.0.0 to
*1
IP address
255.255.255.255
Host link service A
0=TCP/IP
*2
protocol
1=UDP/IP
Port No.: 12289
Host link service A
protocol command
0=ASCII format
*2
data type
Port No.: 12289
Host link service B
0=TCP/IP
*2
protocol
1=UDP/IP
Port No.: 12291
Host link service B
protocol command
0=ASCII format
*2
data type
Port No.: 12291
0 = Not protected
*3
Write protection
1 = Protected
*1
Adjust the settings with GOT settings.
7.3.2
Ethernet setting
*2
For the port No. of the GOT, set the port No. of the host link
service to be used.
7.3.2
Ethernet setting
*3
Set this as necessary.
Description
Set the IP address of the
connected Ethernet module.
Select the protocol to be used
*1
in the port A of the host link
*1
service via Ethernet.
Select the command data type
to be used in the port A of the
host link service via Ethernet.
Select the protocol to be used
*1
in the port B of the host link
*1
service via Ethernet.
Select the command data type
to be used in the port B of the
host link service via Ethernet.
Disables the write command to
this module with the host link
service via Ethernet.
7.3.7
Precautions
Device range
When performing monitoring with the GOT connected
to a YOKOGAWA PLC and setting devices for objects,
use devices within the device range of the
YOKOGAWA PLC.
When a device outside the range is set on an object, an
indefinite value is displayed on the object.
(No error is displayed in the system alarm.)
For details on the device range of YOKOGAWA PLCs,
refer to the following manual:
7.4 Device Range that Can Be Set
When setting IP address
Do not use "0" and "255" at the end of an IP address.
(Numbers of *.*.*.0 and *.*.*.255 are used by the
system.)
The GOT may not monitor the controller correctly with
the above numbers.
Consult with the administrator of the network before
setting an IP address to the GOT and controller.
When connecting to multiple GOTs
(1) Setting Station
When connecting two or more GOTs in the Ethernet
network, set each [Station] to the GOT.
7.3.2 ■ Ethernet setting
(2) Setting IP address
Do not use the IP address "192.168.0.18" when using
multiple GOTs.
A communication error may occur on the GOT with the
IP address.
When connecting to the multiple network
equipment (including GOT) in a segment
By increasing the network load, the transmission speed
between the GOT and PLC may be reduced.
The following actions may improve the communication
performance.
• Using a switching hub
• More high speed by 100BASE-TX (100Mbps)
• Reduction of the monitoring points on GOT
7. CONNECTION TO YOKOGAWA PLC
7.3 Ethernet Connection
7
7 - 21