• (For 32 bits)
Monitor and write only b8 to b15 and b24 to 31 of the buffer memory.
Example:
The monitor value is 00870043H when monitoring BM0=87654321H as mask type 6.
BM0=65002100H when writing input value 87654321H to BM0=00000000H as mask type 6.
(5) Setting of the module No. (MELSEC-FX)
Set the module No. of the special function unit or special function block to monitor or write.
The module No.0 to No.7 are assigned in order for the nearest module or block from the main unit. For details of the
module No., refer to the following.
(a)
Direct specification
Specify the module No. (No.0 to No.7) of the special function unit or special function block directly, to monitor or
write when setting the devices.
(b)
Indirect specification
Specify the module No. of the special function unit or special function block indirectly, to monitor or write when
setting the devices, by using the 16-bit GOT internal data register (GD10 to GD25).
When specifying the station No. from 100 to 115 on GT Designer3, the value of GD10 to GD25 corresponding to
the module No. will be the module No. of the special function unit or special function block.
Module No.
100
101
114
115
*1
2 - 12
BM0
Monitor value
Input value
BM0
(Before writing)
BM0
(After writing)
User's Manual (Hardware) of MELSEC-FX
*1
Compatible device
GD10
GD11
:
:
GD24
GD25
The module No. cannot be specified indirectly for the multi-drop connection.
8
7
6
5
4
3
2
0
0
8
7
0
0
4
8
7
6
5
4
3
2
0
0
0
0
0
0
0
6
5
0
0
2
1
0
0 to 7
For the setting other than the above, error (dedicated device is out of range)
will occur.
If a non-existent module No. is set, a timeout error occurs.
1
H
3
H
1
H
0
H
0
H
Setting range