(4) GOT Side Settings
Set GT Designer3 as follows.
Setting item
Controller Type
Device setting (Network setting)
Ethernet setting
MELSEC Redundant Setting
(5) Monitoring target change when system switching occurs in a redundant system
• Redundant system-1
When the system switching occurs, CPU (PLC station No.: 2) takes over the control of the Ethernet network
system as the control system.
The GOT automatically starts monitoring accroding to the specified system.
• Redundant system-2
When the system switching occurs, CPU (PLC station No.: 4) takes over the control of the Ethernet network
system as the control system.
The GOT automatically starts monitoring accroding to the specified system.
4 - 12
4.1 MELSEC iQ-R Series
MELSEC iQ-R, RnMT/NC
Host
Host (The control system is monitored.)
NW No.: 1
Other
Station No.: Station number of the control system
The system (control system/standby system) of the the monitor target can
be speified.
Control system/
Only when checking [Enable Redundant Function] in the following
standby system
[MELSEC Redundant System Setting], [Control System/Standby System]
can be set.
5. ETHERNET CONNECTION
4.3 MELSEC Redundant Setting
Contents of setting
Model