To view a list of remote daemons configured for a GOOSE tunnel, type:
show running-config tunnel l2tunneld goose tunnel name remote-daemon
Where:
• name is the name of the GOOSE tunnel
If tunnels have been configured, a table or list similar to the following example appears:
ruggedcom# show running-config tunnel l2tunneld goose tunnel 1 remote-daemon
tunnel
l2tunneld goose tunnel 1
remote-daemon 192.168.10.2
!
!
!
If no remote daemons have been configured, add daemons as needed. For more information, refer to
Section 12.5.5.2, "Adding a Remote
Section 12.5.5.2
Adding a Remote Daemon
To configure a remote daemon for a GOOSE tunnel, do the following:
1.
Make sure the CLI is in Configuration mode.
2.
Add the remote daemon by typing:
tunnel l2tunneld goose tunnel remote-daemon address
Where:
• address is the IP address of the remote daemon
Type commit and press Enter to save the changes, or type revert and press Enter to abort.
3.
Section 12.5.5.3
Deleting a Remote Daemon
To delete a remote daemon, do the following:
1.
Make sure the CLI is in Configuration mode.
2.
Delete the remote daemon typing:
no tunnel l2tunneld goose tunnel name remote-daemon address
Where:
• name is the name of the GOOSE tunnel
• address is the IP address of the remote daemon
Type commit and press Enter to save the changes, or type revert and press Enter to abort.
3.
Viewing a List of Remote Daemons