CLI User Guide
Parameter
rtu-list { rtu-list }
Type commit and press Enter to save the changes, or type revert and press Enter to abort.
4.
Section 10.2.6
Configuring the Raw Socket Protocol
To configure the raw socket protocol for a serial port, do the following:
1.
Make sure the CLI is in Configuration mode.
Navigate to interface » serial » {interface} » protocols » rawsocket, where {interface} is the serial port.
2.
3.
Configure the following parameter(s) as required:
Parameter
pack-char { pack-char }
pack-timer { pack-timer }
pack-size { pack-size }
turnaround { turnaround }
call-direction { call-direction }
max-connection { max-connection }
remote-ip { remote-ip }
remote-port { remote-port }
local-ip { local-ip }
Configuring the Raw Socket Protocol
Synopsis:   A string
The ID of the RTU(s) connected to the serial port. Specify multiple RTUs with a space
(e.g. 1 2 3 4) or a comma and space (e.g. 1, 2, 3, 4). A strictly comma-separated list (e.g.
1,2,3,4) is not permitted.
This parameter is mandatory.
Synopsis:   { off } or a 32-bit signed integer between 0 and 255
Default:   off
The numeric value of the ASCII character which will force forwarding of accumulated
data to the network.
Synopsis:   A 32-bit signed integer between 5 and 1000
Default:   1000
The delay from the last received character until when data is forwarded.
Synopsis:   { max } or a 32-bit signed integer between 16 and 1400
Default:   max
The maximum number of bytes received from the serial port to be forwarded.
Synopsis:   A 32-bit signed integer between 0 and 1000
Default:   0
The amount of delay (if any) to insert between the transmissions of individual messages
out the serial port.
Synopsis:   { in, out, both }
Default:   out
Whether to accept an incoming connection, place an outgoing connection or do both.
Synopsis:   A 32-bit signed integer between 1 and 32
Default:   1
The maximum number of incoming connections to permit when the call direction is
incoming.
Synopsis:   A string 7 to 15 characters long or a string 6 to 40 characters long
The IP address used when placing an outgoing connection.
Synopsis:   A 32-bit signed integer between 1024 and 65535
The TCP destination port used in outgoing connections.
Synopsis:   A string 7 to 15 characters long or a string 6 to 40 characters long
The IP address used to establish a connection. Leaving it blank allows an incoming
connection to any interface.