Chapter 10
Serial Server
Parameter
aging-timer { aging-timer }
max-connection { max-connection }
4.
Add a Device Address table. For more information about adding Device Address tables, refer to
Section 10.3.2, "Adding a Device Address
Type commit and press Enter to save the changes, or type revert and press Enter to abort.
5.
Section 10.2.5
Configuring the Modbus TCP Protocol
To configure the modbus TCP protocol for a serial port, do the following:
1.
Make sure the CLI is in Configuration mode.
2.
Navigate to interface » serial » {interface} » protocols » tcpmodbus » settcpmodbus, where {interface} is
the serial port.
3.
Configure the following parameter(s) as required:
Parameter
response-timer { response-timer }
pack-timer { pack-timer }
turnaround { turnaround }
retransmit { retransmit }
max-connection { max-connection }
local-port { local-port }
334
Synopsis:   A 32-bit signed integer between 60 and 10800
Default:   1000
The length of time a learned DNP device in the Device Address Table may go without any
DNP communication before it is removed from the table.
Synopsis:   A 32-bit signed integer between 1 and 32
Default:   1
The maximum number of incoming DNP connections.
Table".
Synopsis:   A 32-bit signed integer between 50 and 10000
Default:   100
The maximum time from the last transmitted character of the outgoing poll until the
first character of the response. If the RTU does not respond in this time, the poll will have
been considered failed.
Synopsis:   A 32-bit signed integer between 5 and 1000
Default:   1000
The maximum allowable time to wait for a response to a Modbus request to complete
once it has started.
Synopsis:   A 32-bit signed integer between 0 and 1000
Default:   0
The amount of delay (if any) to insert after the transmissions of Modbus broadcast
messages out the serial port.
Synopsis:   A 32-bit signed integer between 0 and 2
Default:   0
The number of times to retransmit the request to the RTU before giving up.
Synopsis:   A 32-bit signed integer between 1 and 32
Default:   1
The maximum number of incoming connections.
Synopsis:   A 32-bit signed integer
Default:   502
The alternate local TCP port number. If this field is configured, a single connection
(per serial port) may be made to this alternate port number. Note that Modbus TCP
uses a default local port number of 502. There is no limit imposed on the number of
connections to the default TCP port.
Description
Description
Configuring the Modbus TCP Protocol
RUGGEDCOM ROX II
CLI User Guide